in Russianin Englishin Finnish

AutoLog® OEM-PLCs
Introduction | AL-4 | AL-8 | AL-10SP | AL14LP | AL-16 | AL-20 | AL-32 | AL2000S |

AutoLog® 8

There are two models of AL8, the standard model, called AL8, and the model with integrated GSM modem, called AL8 with GSM. Technical features of these models are same, except the parts marked as " ** " in this web page. Note! AL8 with GSM is different model than AutoLog® GSM-8, which belongs to AutoLog® GSM-RTU product family.


Digital inputs (DI) 4 pcs
12/24 VDC / max. 8 mA / PNP / opto-isolated
Digital outputs (DO) 2 pcs
12/24VDC / max. 2A / NPN / opto-isolated
Relay outputs (RO) 2 pcs
12-24 VDC / max. 3A , 24-230 VAC
Analog inputs (AI) 0-2 pcs, plug-in analog input modules
Pt100, KTY10, 0-5V, 0-10V, 0-20mA, 4-20mA, RMS, jne.
Serial ports** 2 pcs
SER1: RS232, (RJ45) / integrated GSM modem**
SER2: RS232/485*, supports AutoLog® Serial Plug-in modules.
Modbus RTU -communication Modbus can run simultaneously in both serial ports. Independent setting for both serial ports,
Master/Slave, 300-115200bps
I2C-port HMI, iButton, etc.
HMI -user interface Local user interface can be connected through I2C-port or serial port. Variety of different models from small, character displays to multi-featured Windows CE based graphical touchscreens, with Web Studio SCADA development tool support. Look more from AutoLog® HMI -pages.
Battery backup Yes
Application program capacity 512kB FLASH, 8000 programming lines
Program instructions / functions Over 260 instructions / functions
Logical, arithmetic, comparison, timer/counter, sequence program, reporting, queue, FIFO, PID...
PID controllers 32 build-in PID controllers
Programming tool (PC) (AutoLog®) ALProWin, instruction list & ladder, symbolic names, trends, monitoring tables, binary and Modbus programming.
Remote programming PLCs can be programmed remotely through any transmission media, which supports Modbus protocol. e.g. Radio Network, GSM Data, RS-485.
Data memory RAM 512kB
Data logging PLC can save time-stamped measurement or any data into its memory. E.g. 10 time-stamped measurements x 3000 records.
Clock/Calendar Yes (can be set remotely)
UPS connector Yes
GSM/GPRS modem** Integrated GSM/GPRS modem only in AL8 with GSM -model. GSM application programming is more difficult than in AutoLog® GSM-RTUs. Ask more!
Enclosure Default: DIN -rail mounting with metal cover, IP20
Opt 2 : plastic box, IP65
Opt 3: metal box. Ask more!
Size (w x h x d) AL8: 190 x 125 x 65 mm
AL8 w GSM (same)
Weight ~0,4 kg
Operating temperature** AL8: -30...+70 °C
AL8 w GSM: 0...+55 °C
Storage temperature** AL8: -40...+80 °C
AL8 w GSM: -30...+65 °C
Power supply 12 / 24VDC or 10/18VAC max. 5VA
EMC Immunity according to EN50082-1 & EN50082-2
Emissions according to EN50081-1 & EN50081-2

* RS-485 needs optional AutoLog® Serial plug-in module
** This feature is only in AL8 with GSM -model

Order information:

AutoLog® 8
 
product name description code
AL8 AutoLog® 8 PLC ask
AL8 w GSM AutoLog® 8 PLC with integrated GSM modem. ask


Optional modules and accessories:
 
SCADA, control room software Web Studio / any SCADA on market that supports Modbus ( 99% of SCADAs support Modbus RTU protocol). Look Web Studio!
Analog input modules Pt100 ( -50..150°C )
Pt100 ( 0..500°C )
Pt100 ( -250..750°C )
0..5mA
0..20mA
4..20mA,
KTY10 (50..150°C),
NTC (-5..50°C),
0..2V,
0..5V,
0..10V,
-10..10V,
RMS 40VAC
RMS 25VAC
RMS 0.25VAC
900781
900782
900784
900795
900799
900800
900797
900796
900788
900785
900786
900790
900809
900807
900808
Touch screens
(serial port connection)
AL57CE-HMI  (WinCE 5.7" SNT QVGA)
AL121CE-HMI (WinCE 12.1" TFT SVGA)
(Supports Web Studio SCADA development tools)
945122
945124
 
HMI interfaces
(I2C -port connection)
AL1093F (2 x 16 characters)
AL1095A (8 x 21 characters / 128 x 64 pixels)
900860
900850
ALProWin PC based AutoLog® PLC programming tool 941020
RS232/485 SP-i RS232/485 converter, Serial Plug-in module
(SP-i = Serial Plug-in)
901165
RS232/485 SP-i Iso RS232/485 converter, Serial Plug-in module, Isolated 901157
ModbusTCP SP-i ModbusRTU/ModbusTCP (Ethernet) protocol gateway, Serial Plug-in module 900065
EthLAN SP-i Web server with Ethernet LAN connection, Serial Plug-in module ask
WLAN SP-i Web server with Wireless LAN connection, Serial Plug-in module ask
Wireless I/O Wireless I/O master module, ask more ask
Radio modem External radio modem for wireless communicating and also remote programming of PLC. ask
GSM modem** Integrated GSM/GPRS modem only in AL8 with GSM -model. ask


Please call or send e-mail to get more information!

FF-Automation
Eräkuja 2
01600 Vantaa
Finland
Tel: +358 10 2190 500